Valve Cv — Companion Article
Open the tool: https://pipingdesigners.com/tools-training/valve-cv/
What this tool does
Valve Cv works out the basic flow coefficient for a valve, as Cv or Kv. It handles non-choked liquid flow, warns when a liquid may choke, and gives a simple gas estimate from the inlet density.
When to use it
Use it for a quick check of valve size, or to read a vendor’s Cv against your flow. Final control valve sizing needs the vendor’s software and the full method.
Inputs
- Fluid: liquid or gas.
- Liquid: flow, specific gravity and pressure drop. Optionally FL, inlet pressure, vapour pressure and critical pressure for the choked check.
- Gas: standard flow, pressure drop, inlet absolute pressure, inlet temperature and molecular weight. Optionally Z, xT and the specific-heat ratio.
- Units: metric or US customary.
How it works
For liquids, Cv = Q √(G / ΔP) with gpm and psi, and Kv = Q √(G / ΔP) with m³/h and bar. Cv = Kv / 0.865.
If you add FL and the pressures, the page works out the choked limit FL² × (P1 − FF × Pv). A drop above that is flagged, and the result is not a sizing result.
For gas, the page converts the flow to actual conditions, works out the inlet density, and uses the liquid form with that density.
Understanding the result
Pick a valve whose Cv at your opening is above the result, with margin. If a warning appears, the simple result does not apply.
Engineering considerations
- The gas estimate only holds for small drops. Above 0.3 of the inlet absolute pressure, the page says it does not apply.
- The expansion factor is not applied, and neither are piping geometry factors for reducers.
- Flashing and cavitation need the vendor’s review.
Example
10 US gpm of water across 4 psi gives Cv 5. 10 m³/h of water across 4 bar gives Kv 5.
Standards/references (licensed vs interim)
The liquid form is the common basic equation. The full method is in the IEC 60534 series and the ISA equivalent. The page does not apply the full method or copy any table.
Limitations/disclaimer
- Basic, non-choked sizing only.
- No expansion factor and no piping geometry factors.
- The result is preliminary and needs engineering review.
Use the tool
Calculate now: Valve Cv
Related tools
- The line sizing tool. Read the line sizing companion article.
- Valve face-to-face, for valve lengths (new tool, being added to the site).